Gas test apparatus
3-032-R003
Dimensions::
- Width: 14.4 inches
- Height: 5.9 inches
- Depth: 11.2 inches
- Weight: 15 pounds
Basic Equipment:
- Transport case
- Measuring device for decomposition products
- graduated cylinder
- pressure gauge
- mounting for test tube
- 10 individual. test tubes
- Connecting couplings in DN. 8 and DN 20
- Connecting hose 2 m (6.6 ft) long
Description:
Decomposition products which are produced by an arc in the SF6 can be determined in parts per million by volume from 1 to 18 ppm with the measuring device for decomposition products 3-032-R001. By sampling a given volume of SF6, at a given pressure and rate, a change in the test tube color indicates the presence (and quantity) of decomposition products in the test gas. The test chamber is filled with a sample of the gas to be tested, to a pressure of approximately 29 psi. The pressure is indicated by a built-in pressure gauge. Once the test chamber has been pressurized, a test tube is inserted into the exhaust port of the test chamber. When the exhaust valve is opened, and the test gas passes throughout the tube, a distinct change of color within the tube can be observed (if there is decomposition present). The gas flow is stopped once the pressure within the test chamber reaches approx. 15 psig. By reading the graduated marks on the tube, the operator can determine exactly how much decomposition is present within the sampled gas.
3-033-R002
SPECIFICATION
Power Supply: 3V DC; two “C” cell Alkaline batteries
Maximum Sensitivity: SF6 @ 0.5 oz/yr. (14g/yr)
Operating Temperature: 30° to 125° F (0°to 52° C)
Battery Life: Approximately 30 hours normal use
Duty Cycle: Continuous, no limitation
Response Time: Instantaneous
Reset Time: One second
Warm-Up Time: Approximately 2 Seconds
Unit Weight: 1.2 lbs (560 grams)
Unit Dimensions: 9" x 2.5" x 2.5" (22.9 cm x 6.5cm x 6.5cm)
Fixed Probe Length: 14" (35.5 cm)
|
3-037-R001
Description:
The 3-037-R002 moisture measuring device was designed, from the ground up, to be used on arced SF6. Unlike conventional multi-gas hygrometers, the 3-037 is specifically calibrated for the unique characteristics (i.e. densities, molecular weights, and acidity) of faulted SF6. Not only is the device consistently more accurate and reliable, but the typical long-term drift (and subsequent need for factory recalibration) associated with non gas-specific devices is all but eliminated.
The exclusive DILO sensor measures SF6 at atmospheric pressure which removes pressure and temperature variables from moisture readings. Additionally, the electronic flow meter not only reduces the sample to a trickle, but the orientation of the device is no longer relevant – making the 3-037 far more suitable for on-site testing. All readings are displayed in parts per million by volume (PPMv).
Technical data:
measuring range: 41p PPMv – 10,000 PPMv
measuring accuracy: ± 2 °C (±4 °F)
max. input pressure: pe 10 bar (145 PSIG)
operating temperature: 0 - 40 °C (32 °F - +104 °F)
operating voltage: 100 – 240 V 50/60 Hz